A small town runs on one natural-gas plant. Add wind turbines, solar farms and a battery, then scrub through a 24-hour day to see who supplies each megawatt, when the battery charges or discharges, and how much of the demand renewables actually cover.
The vertical bar is the town's substation bus. At every instant, power flowing in must equal power flowing out: gas + wind + solar + battery discharge = town demand + battery charging. The grid has almost no storage of its own, so something has to adjust second by second. In this model, that's the battery first and the gas plant second.
Each plant produces power at a lower voltage and a step-up transformer lifts it onto the bus. That's the same symbol you learned in the distribution one-line, just used at the generation end.
Solar panels and batteries are DC devices. The box labeled DC/AC is an inverter, which converts their output into grid-synchronized AC. The battery's inverter works in both directions (it's often called a PCS, power conversion system), which is why the battery line can reverse.
Each box shows its nameplate (the most it can ever make) and its output right now. The gap between the two is the whole story of capacity factor. Try scrubbing to 3 AM, noon, and 7 PM.
Start with a scenario, then change one thing at a time. Drag across the chart or use the time slider to move through the day; everything below the slider describes that moment. The day is ninety-six fifteen-minute slices, and every slice has to balance to zero.
MWh is the energy capacity: the total amount the battery can store.
MW is the power rating: the most it can charge or discharge at any moment. At that rate a full battery takes about hours to empty (before losses).
Usable window –% means the simulation never lets the battery fall below or rise above those levels, which are the two dashed lines on the chart. Real batteries are kept out of the extremes to protect their lifespan, so only the middle is used: MWh, between and MWh. That is why the curve flattens at the top line when the battery is full and at the bottom line when it is empty.
The bars show charging and discharging power: hatched bars are charging, solid bars are discharging.
Every number in the playground comes from the formulas below. The underlined values are live: they update with your current settings and the time on the slider.
Many states, like Washington, have clean energy mandates that get closer every year. Utilities are working to replace aging coal plants with renewable generation like wind and solar. But swapping one plant for another is harder than it sounds. A replacement has to match how much energy the old plant produced over a year, and how much power it can be counted on to deliver at peak demand. Matching its size on paper isn’t enough.
Build a replacement and see which resources can do which job.
Start with the obvious swap.The plant is 500 MW, so build 500 MW of wind?
Planning for 2030 in Washington. Costs from NLR's ATB, capacity credits from WRAP.
Energy = MW × 8,760 h × capacity factor . Reliable = MW × capacity credit .
| Input | Value | Source |
|---|
Educational simulator, not a formal resource adequacy or production-cost study.
A new plant is built. Now it has to get in line. Next: Interconnection queues →